Wieland SNO 4083, 115V ac, 230 V ac Safety Relay, 3 Safety Contacts

Image representative of range

Subtotal (1 unit)*

£336.03

(exc. VAT)

£403.24

(inc. VAT)

Add to Basket
Select or type quantity
In Stock
  • 9 unit(s) ready to ship
  • Plus 2 unit(s) shipping from 14 May 2026
  • Plus 2 unit(s) shipping from 08 July 2026
Need more? Click ‘Check delivery dates’ to find extra stock and lead times.
Units
Per unit
1 +£336.03

*price indicative

RS Stock No.:
780-5082
Mfr. Part No.:
R1.188.3590.0
Brand:
Wieland
Find similar products by selecting one or more attributes.
Select all

Brand

Wieland

Product Type

Safety Relay

Safety Contacts

3

Reset Method

Manual

Mount Type

DIN Rail

Series

SNO 4083

Power Consumption

4VA

Terminal Type

Screw

Time Delay

1.5 s

IP Rating

IP20, IP40

Switching DC Voltage

24V dc

Switching AC Voltage

230V ac

Minimum Operating Temperature

-25°C

Contact Current

6A

Standards/Approvals

EN 50156-1, EN 62061, EN 81-1, EN ISO 13849-1

Maximum Operating Temperature

65°C

Length

96.5mm

Width

22.5mm

Height

114mm

Hazardous Area Certification

No

Safety Category

CAT 4, ISO 13849-1

Coil Voltage

115, 230V ac

Wieland SNO 4083KM Safety Relay


SNO 4083KM Safety Relay Function - after the supply voltage is applied to terminals A1/A2 and the safety inputs are closed, the enabling current paths (NO contacts) are closed and the signal current path (NC contact) is opened automatically or by pressing the reset button (manual monitored start). When the safety inputs are opened/de-energized the enabling current paths (NO contacts) are opened immediately and the signal current path (NC contact) is closed.

The SNO 4083KM safety relay requires fewer connection cables, irrespective of whether operation with or without cross monitoring is desired. The two channel control of the SNO 4083KM is carried out by either an NC/NC or an NC/NO combination of the safety sensor. In the case of two channel control of the device, a synchronous time is automatically monitored between the two channels. The SafeStart function is used with a manual start, the reset input is automatically monitored for a rising and falling signal edge. The Monoflop function is integrated into the safety relay and prevents device interlocking under all circumstances. Simple diagnosis is possible thanks to an intelligent display system that shows the user the different operating modes of the safety relay in its different applications.

Monitoring of E-Stop, Safety Gate and Light Barrier applications

Stop Category 0 according to EN 60204-1

Single channel or two channel control

Two-channel control with NC/NC or NC/NO

Manual or automatic start

Cross monitoring

Synchronous time monitoring for two channel control

3 enabling current path / 1 signalling current path

Screw terminals, pluggable

Up to PL e / Category 4 (EN ISO 13849-1)

Up to SILCL 3 (EN 62061)

Related links