Specifications
Technical Reference
Legislation and Compliance
Product Details
Find similar products by selecting one or more attributes.
Select all | Attribute | Value |
|---|---|---|
| Brand | EPCOS | |
| Height | 985mm | |
| Number of Phases | 1 | |
| Series | MV APP | |
| Mounting Type | Stud Mount | |
| Voltage | 36000V ac | |
| Length | 350mm | |
| Dielectric Material | Polypropylene | |
| Capacitance | 500nF | |
| Width | 160mm | |
| Minimum Operating Temperature | -25°C | |
| Weight | 52kg | |
| Select all | ||
|---|---|---|
Brand EPCOS | ||
Height 985mm | ||
Number of Phases 1 | ||
Series MV APP | ||
Mounting Type Stud Mount | ||
Voltage 36000V ac | ||
Length 350mm | ||
Dielectric Material Polypropylene | ||
Capacitance 500nF | ||
Width 160mm | ||
Minimum Operating Temperature -25°C | ||
Weight 52kg | ||
- COO (Country of Origin):
- IN
Oil impregnated all-polypropylene capacitor (APP)
Cost effective solution to protect valuable MV assets
Highly reliable design wit edge folding construction
Stainless steel container
Temperature category: -25/D
Internal discharge device
Paint shade of container: light grey
Applications
Surge suppression in MV grids
Protection of MV equipment such as generators, motors, transformers and reactors by reducing dv/dt and smoothening voltage distribution across the winding
Damps reflected waves within winding
Protection of mechanical and solid state switching devices from malfunction like pre-strike, post-strike and insulation failure
Reduction of switching-off transients caused by inductive current chopping through vacuum or other switchgear
Prevention of malfunction of relays and protection schemes due to transients
Cost effective solution to protect valuable MV assets
Highly reliable design wit edge folding construction
Stainless steel container
Temperature category: -25/D
Internal discharge device
Paint shade of container: light grey
Applications
Surge suppression in MV grids
Protection of MV equipment such as generators, motors, transformers and reactors by reducing dv/dt and smoothening voltage distribution across the winding
Damps reflected waves within winding
Protection of mechanical and solid state switching devices from malfunction like pre-strike, post-strike and insulation failure
Reduction of switching-off transients caused by inductive current chopping through vacuum or other switchgear
Prevention of malfunction of relays and protection schemes due to transients