Schneider Electric EMI Filter Motor Choke for Use with Altivar 12, Altivar 312, Altivar 312 Solar, Altivar 31C, Altivar

Subtotal (1 unit)*

£231.78

(exc. VAT)

£278.14

(inc. VAT)

Add to Basket
Select or type quantity
In Stock
  • 5 unit(s) ready to ship
  • Plus 1 unit(s) ready to ship from another location
  • Plus 1 unit(s) shipping from 07 November 2025
Need more? Click ‘Check delivery dates’ to find extra stock and lead times.
Units
Per unit
1 +£231.78

*price indicative

RS Stock No.:
797-0785
Mfr. Part No.:
VW3A4552
Brand:
Schneider Electric
Find similar products by selecting one or more attributes.
Select all

Brand

Schneider Electric

Accessory Type

Choke

For Use With

Altivar 12, Altivar 312, Altivar 312 Solar, Altivar 31C, Altivar 32, Altivar 61, Altivar 71, Lexium 05

Electrical Phase

3

Length

155mm

Depth

90mm

Dimensions

155 x 130 x 90 mm

COO (Country of Origin):
HU

Altivar AC Line Choke


A line choke can be used to provide improved protection against overvoltages on the line supply and to reduce the current harmonics produced by the drive. The recommended chokes can be used to limit the line current. They have been developed in line with standard EN 50178 (VDE 0160 level 1 high energy overvoltages on the line supply). The inductance values are defined for a voltage drop between phases of between 3% and 5% of the nominal line voltage. Values higher than this will cause loss of torque. These chokes should be installed upstream of the drive.

The use of line chokes is recommended in particular under the following circumstances:
Close connection of several drives in parallel
Line supply with significant disturbance from other equipment (interference, overvoltages)
Line supply with voltage imbalance between phases above 1.8% of the nominal voltage
Drive supplied by a line with very low impedance (in the vicinity of a power transformer 10 times more powerful than the drive rating)
Installation of a large number of frequency converters on the same line
Reduction of overload in cos Ø correction capacitors, if the installation has a power factor correction unit