Chauvin Arnoux F407 Clamp Meter Bluetooth, 1500A dc, Max Current 1000A ac CAT III 1000V With RS Calibration

Currently unavailable
Sorry, we don't know when this will be back in stock.
RS Stock No.:
766-2863
Mfr. Part No.:
P01120947
Brand:
Chauvin Arnoux
Find similar products by selecting one or more attributes.
Select all

Brand

Chauvin Arnoux

Absolute Maximum AC Current Measurement

1000A ac

Absolute Maximum DC Current Measurement

1500A dc

Absolute Maximum AC Voltage Measurement

1400V ac

Absolute Maximum DC Voltage Measurement

1400V dc

Absolute Maximum Resistance Measurement

99.99W

Connectivity

Bluetooth

Model Number

F407

Calibrated

RSCAL

AC Current Measurement Resolution

10mA

DC Current Measurement Resolution

10mA

Best DC Current Accuracy

±1% + 3 Digits

Clamp Meter Type

Power/Harmonics Clamp Meter

Best AC Current Accuracy

±1% +3 digits

Best AC Voltage Accuracy

±1% + 3 Digits

Jaw Capacity Busbars

48mm

Functions Measured

AC Current, AC Voltage, DC Current, DC Voltage, Resistance, Temperature

True RMS

Yes

Best DC Voltage Accuracy

±1% + 3 Digits

AC Voltage Measurement Resolution

10mV

Maximum Conductor Size

48mm

Battery Life

350 h

Weight

600g

Safety Category Level

CAT III, CAT IV

Minimum Operating Temperature

-20°C

Height

41mm

DC Voltage Measurement Resolution

10mV

Dimensions

92 x 41 x 272mm

Resistance Measurement Resolution

100mΩ

Length

272mm

Width

41mm

Power Source

Battery

Maximum Operating Temperature

+55°C

Display Type

Backlit LCD

Battery Type

AA

Safety Category

CAT III 1000 V, CAT IV 1000V

Safety Category Voltage

1000V

COO (Country of Origin):
CN

F407 Power and harmonics Clampmeter


The F407 clampmeter is designed for medium-power low-voltage applications in sectors such as LV electricity production and distribution, industry, railways
This clamp multimeter is also suitable for lift/elevator technicians and other lifting and transport specialists
The applications for the clamp multimeter are maintenance, testing, monitoring, diagnostics and connection
Equipped with a fast 12-bit TRMS digital acquisition system
The large backlit display makes it easy to read in all circumstances
Automatic AC/DC detection
AC and DC voltage up to 1000 V
W/VA/var, PF and DPF power values
THD-f and THD-r
Harmonics up to 25th order
Resistance and audible continuity
Min, Max and Peak± analysis on all functions
TrueInrush current measurement
Data recording
Bluetooth interface and PC software
IP54 protection

Related links