PR Electronics 2 Channel Galvanic Barrier, Pulse Isolator, Relay Output, ATEX, IECEx

Subtotal (1 unit)*

£229.98

(exc. VAT)

£275.98

(inc. VAT)

Add to Basket
Select or type quantity
In Stock
  • 16 unit(s) ready to ship
  • Plus 7 unit(s) shipping from 21 October 2025
Need more? Click ‘Check delivery dates’ to find extra stock and lead times.
Units
Per unit
1 +£229.98

*price indicative

RS Stock No.:
136-8696
Mfr. Part No.:
5202B4
Brand:
PR Electronics
Find similar products by selecting one or more attributes.
Select all

Brand

PR Electronics

Number of Channels

2

Module Type

Pulse Isolator

Barrier Type

Galvanic Barrier

Output Signal Type

Relay

Maximum Voltage

253 V ac, 300V dc

Hazardous Area Certification

ATEX, IECEx

Supply Voltage

19.2 → 300 V dc, 21.6 → 253V ac

Minimum Operating Temperature

-20°C

Maximum Operating Temperature

+60°C

Safety Current Maximum

400mA

Safety Voltage Maximum

253 V ac, 300 V dc

Series

5200

Operating Temperature Range

-20 → +60°C

COO (Country of Origin):
DK

PR Electronics 5202B Ex Pulse Isolator


PR Electronics 5202B pulse isolator for transmission of signals to the safe area from NAMUR sensors installed in hazardous areas. This signal conditioning isolator measures one or more pulse inputs and provides an identical number of isolated pulse outputs. The PR 5202B uses transformer and optical isolation techniques to provide 3.75 kVac galvanic isolation between the input, output and power terminals. The high level of electrical isolation means that input pulses sensed at the 5202B are not electrically connected to the output pulse. The 5202B has been designed, developed and certified for use in SIL 2 applications according to the requirements of IEC 61508.
Besides providing isolation, the PR 5202B is a barrier. This means that the module can make an intrinsically safe measurement of contacts and NAMUR sensors mounted in a zone 0/ Division 1 explosion hazard area. The PR 5202B limits the level of energy present at the contact or the NAMUR sensor to a low intrinsically safe level, thereby preventing ignition of a flammable atmosphere around the sensor – even if the sensor or the cable is damaged.

Features and Benefits


• 3.75 kVac galvanic isolation between input, output and supply
• One input signal can be used on two separate outputs
• A cable error alarm can be detected on a separate output
• Designed, developed and certified for use in SIL 2 applications
• Front LED indicates operation status and malfunction
• DIN rail mounting


PR Electronics - Ex Interfaces

Related links