Eaton AFDD, 13A Current Rating, 2P Poles, 30mA Trip Sensitivity, Type B, AFDD+ Range

Subtotal (1 unit)*

£192.21

(exc. VAT)

£230.65

(inc. VAT)

Add to Basket
Select or type quantity
Temporarily out of stock
  • Shipping from 15 December 2025
Need more? Click ‘Check delivery dates’ to find extra stock and lead times.
Units
Per unit
1 +£192.21

*price indicative

RS Stock No.:
146-2817
Mfr. Part No.:
187180 AFDD-13/2/B/003-A
Brand:
Eaton
Find similar products by selecting one or more attributes.
Select all

Brand

Eaton

Current Rating

13A

Range

AFDD+

Number of Poles

2

Trip Sensitivity

30mA

Circuit Breaker Type

AFDD

Tripping Characteristics

Type B

Rated AC Voltage

240V

Mounting Style

DIN Rail Mount

Earth Leakage Protection Type

AC

Application

Commercial, Residential

Reset Actuator Type

Toggle Switch

Terminal Contact Type

Screw

Overall Width

80mm

Overall Depth

70mm

Breaking Capacity at Maximum Voltage Rating

10 kA

Break Time

Instantaneous

Overall Length

54mm

Overall Dimensions

54 x 70 x 80mm

COO (Country of Origin):
CZ

AFDD


Professional range of Eaton AFDD+ RCBOs for Type B distribution boards. The switch disconnectors are designed for general commercial building applications.

Eaton Arc Fault Detection Device, 2 Pole, Type B - AFDD+ Series - AFDD-13/2/B/003-A


Protect your electrical supply from hazards with this Eaton AFDD (arc fault detection device). This device identifies series and parallel arc faults caused by loose wires and worn contacts. These faults generate heat that melts wire insulation and can potentially start electrical fires. This AFDD also incorporates RCD (residual current device) and MCB (miniature circuit breaker) functionality, for protection against earth faults and short circuits. An LED (light-emitting diode) indicator tells you the cause of a trip by flashing one to six times, with each number indicating a different type of fault.

• DIN rail mounting style saves space and keeps components organised
• Screw terminals ensures reliable connections without the need for special tools
• Compact dimensions of 54 (L) x 70 (D) x 80mm (W)

What types of fault does this AFDD detect?


This device combines the functionality of three types of circuit breakers to trip a circuit if a fault is detected. The AFDD functionality checks for sudden spikes in power resulting from arc faults, while RCD capability looks for line imbalances that could cause electric shocks. The unit's MCB function detects short circuits and overcurrents.

Note

Eaton formerly known as Moeller


Electric Fire Protection Device