PULS Redundancy module, for use with Y Series
- RS Stock No.:
- 627-6253
- Distrelec Article No.:
- 110-64-941
- Mfr. Part No.:
- YR2.DIODE
- Brand:
- PULS
Subtotal (1 unit)*
£63.57
(exc. VAT)
£76.28
(inc. VAT)
FREE delivery for orders over £50.00
In Stock
- 14 unit(s) ready to ship
- Plus 52 unit(s) ready to ship from another location
- Plus 14 unit(s) shipping from 13 October 2025
Need more? Click ‘Check delivery dates’ to find extra stock and lead times.
Units | Per unit |
---|---|
1 + | £63.57 |
*price indicative
- RS Stock No.:
- 627-6253
- Distrelec Article No.:
- 110-64-941
- Mfr. Part No.:
- YR2.DIODE
- Brand:
- PULS
Specifications
Technical Reference
Legislation and Compliance
Product Details
Find similar products by selecting one or more attributes.
Select all | Attribute | Value |
---|---|---|
Brand | PULS | |
Accessory Type | Redundancy Module | |
For Use With | Y Series | |
Select all | ||
---|---|---|
Brand PULS | ||
Accessory Type Redundancy Module | ||
For Use With Y Series | ||
- COO (Country of Origin):
- CZ
YR2.DIODE DC12-48 V, 20 A, Dual Redundancy Module
Dual diode redundancy module for building 1+1 and N +1 redundant power supply systems. It has two input channels which can be connected to 10 A power supplies and one output which can carry nominal currents up to 20 A. The YR2.DIODE is an excellent choice for use in a redundant system if the power supply is equipped with a DC-OK signal.
Features and Benefits
• Two 10 A inputs, one output (20A max.)
• Only 0.85 V voltage drop between input and output under full load
• Full output current between -40 °C and 60°C
• Quick connect spring-clamp terminals
• Reverse polarity protected input
• DC 12 V to 48 V, 20A output
• DC 12 V dc to 48 V dc (±25%) input
• Size: 32 x 124 x 102 mm (W x H x D)
• Weight 290 g
• Only 0.85 V voltage drop between input and output under full load
• Full output current between -40 °C and 60°C
• Quick connect spring-clamp terminals
• Reverse polarity protected input
• DC 12 V to 48 V, 20A output
• DC 12 V dc to 48 V dc (±25%) input
• Size: 32 x 124 x 102 mm (W x H x D)
• Weight 290 g
Product Application Information
A possible application for the diode is to use it to isolate sensitive load circuits with or without alarm signals. This avoids distortion of the power quality which can cause controller failures.
Standards
IEC, UL, EN, SELV
Related links
- PULS Redundancy module, DIMENSION Series
- PULS Redundancy module, CP Series
- PULS Redundancy module, MiniLine MLY Series
- PULS Redundancy module, for use with 20 A Power Supply
- PULS Redundancy module, for use with 40 A Power Supply
- PULS Redundancy module, for use with Power Supplies
- PULS Redundancy module, for use with 1+1 Redundancy with Automated Load Sharing
- PULS Redundancy module 1+1 Redundant Systems