Prysmian FP200 Fire Performance LSZH 1.5 mm² 3 Core Power Cable, White, 50m

Image representative of range

Currently unavailable
We don’t know if this item will be back in stock, it is being discontinued by the manufacturer.

Alternative

This product is not currently available. Here is our alternative recommendation.

1 Reel of 50 Metre(s)

£203.46

(exc. VAT)

£244.15

(inc. VAT)

RS Stock No.:
494-2554
Mfr. Part No.:
20145422
Brand:
Prysmian
Find similar products by selecting one or more attributes.
Select all

Brand

Prysmian

Cross Sectional Area

1.5 mm²

Number of Cores

3

Sheath Colour

White

Length

50m

Cable Type

Fire Performance LSZH

Current Rating

19.5 A

Outer Diameter

8.4mm

Voltage Rating

500 V

Conductor Strand Type

Solid

Conductor Resistance

12.1 Ω/km

American Wire Gauge

15 AWG

Series

FP200

Minimum Operating Temperature

-20°C

Insulation Material

Insudite

Fire Behaviour

Flame Retardant

Maximum Operating Temperature

+70°C

Conductor Material

Annealed Copper

Standards Met

BASEC

RoHS Status: Not Applicable

COO (Country of Origin):
GB

FP 200 Gold Fire Performance Cable


The FP 200 Gold is a hard skin standard fire resistant cable incorporating Prysmian's unique and hard wearing Insudite™ insulation. An excellent, high performance cable for use in fire detection and fire alarm systems, emergency systems and voice alarm systems.

Features and Benefits


LSZH Sheath with Reduced Flame Propagation

Voltage rating 300V/500V

Operating temperature range: -20 to +70°C

Easy to install, requires no bending tools

The red cable is used for fire alarms and the white cable is used for emergency lighting

Laminated aluminium tape screen bonded to sheath and in contact with full size tinned anealed copper circuit protective conductor which provides automatic screen earthing

Product Application Information


Suitable for use in fire alarm wiring, emergency lighting or where mains cable is required to be screened.

Standards

· BS7629-1 Construction of screened fire resistant cables
· BS EN 50200 PH30, PH60, PH120 and ANNEX E
· BS5839-1, 6, 8 & 9 ’standard’ fire resisting cable
· BS5266-1 ’standard’ fire resisting cable
· BS8519 Category 1 control cable
· London Underground 1.085 Approved Product Register (Section 12)

Standards

BS7629-1