Dold Current Monitoring Relay, DPDT, DIN Rail

Image representative of range

Subtotal (1 unit)*

£273.14

(exc. VAT)

£327.77

(inc. VAT)

Add to Basket
Select or type quantity
Temporarily out of stock
  • 2 unit(s) shipping from 03 November 2025
Need more? Click ‘Check delivery dates’ to find extra stock and lead times.
Units
Per unit
1 +£273.14

*price indicative

RS Stock No.:
445-9046
Mfr. Part No.:
IL5882.38 AC/DC24V-230V Tv=5S
Brand:
Dold
Find similar products by selecting one or more attributes.
Select all

Brand

Dold

Monitoring Application

Current

Contact Configuration

DPDT

Mounting Type

DIN Rail

Minimum Current Sensed

10mA

Maximum Current Sensed

10A

Time Delay

0 → 5s

Series

IL 5882

Height

90mm

Length

63mm

Operating Temperature Range

+60°C

Current Range

10 mA → 10A

Maximum Operating Temperature

+60°C

Width

35mm

Minimum Operating Temperature

-20°C

Dimensions

63 x 35 x 90mm

COO (Country of Origin):
DE

Differential current monitor IL 5882


Detection ranges from 30 mA → 10 A with a connected ND 5019 differential current transformer
Programmable for automatic or manual reset after error rectification
Rest current principle
With advance warning
Delete and test buttons
Wire breakage detection
Short reaction time
Adjustable response delay
LED displays for auxiliary voltage and contact position
2 x 1 changeover

Detects insulation faults in earthed networks such as RCCBs but without interruption. For monitoring and preventive maintenance of electrical systems.

Standards

IEC 255, EN 61 557, VDE 0413