Better World
Schneider Electric TeSys F LC1G115 Contactor, 200 → 500 V ac/dc Coil, 4-Pole, 250 A, 1 NO + 1 NC
- RS Stock No.:
- 249-4735
- Mfr. Part No.:
- LC1G1154LSEA
- Brand:
- Schneider Electric
Subtotal (1 unit)*
£682.88
(exc. VAT)
£819.46
(inc. VAT)
FREE delivery for orders over £50.00
In Stock
- 2 unit(s) ready to ship
Need more? Click ‘Check delivery dates’ to find extra stock and lead times.
Units | Per unit |
---|---|
1 + | £682.88 |
*price indicative
Better World
Our Better World range features products that make it easy for you to make a greener product choice you can trust. Click here to find out more.
- RS Stock No.:
- 249-4735
- Mfr. Part No.:
- LC1G1154LSEA
- Brand:
- Schneider Electric
Specifications
Technical Reference
Legislation and Compliance
Product Details
Find similar products by selecting one or more attributes.
Select all | Attribute | Value |
---|---|---|
Brand | Schneider Electric | |
Coil Voltage | 200 → 500 V ac/dc | |
Number of Poles | 4 | |
Contact Current Rating | 250 A | |
Range | TeSys F | |
Series | LC1G115 | |
Function | Load Control | |
Normal State Configuration | 1 NO + 1 NC | |
Better World Product | Yes | |
Better World Verification | Green Premium | |
Select all | ||
---|---|---|
Brand Schneider Electric | ||
Coil Voltage 200 → 500 V ac/dc | ||
Number of Poles 4 | ||
Contact Current Rating 250 A | ||
Range TeSys F | ||
Series LC1G115 | ||
Function Load Control | ||
Normal State Configuration 1 NO + 1 NC | ||
Better World Product Yes | ||
Better World Verification Green Premium | ||
- COO (Country of Origin):
- CN
Schneider Electric LC1G1154LSEA
TeSys Giga high power contactor, 4 poles (4 NO) for category AC-1 applications up to 250A @440V. It provides a 200-500V AC/DC wide band low consumption electronic coil, PLC output control and embedded highly reliability 1NO+1NC auxiliary contact block (17V 1mA). Designed for demanding applications with maximum operating rates up to 600 cycles per hour and environments until 60°C. It procures high reliability and durability with 5 Mcycles mechanical durability. Local and Remote Contact Wear Diagnosis (CWD) as standard function, continuous monitoring with healthy and alarm indicators. It is possibility to replace switching module (main contacts), enhancement contactor life. Contactor can be fixed in all quadrants, maintenance without removing cables/busbars, and OLR could be directly mounted below contactor. To be used with power connection by bolted connection with cable memory kit and control connections by spring terminals, accessible from front for easy and quick replacement. It provides IP2x protection in Front face with shrouds conforming to IEC 60529 and VDE 0106. It can cover -25°C to 60°C operation ambient air temperature and directly mounted on plate, No derating up to 3000m altitude. The dimension is 255mm x 143mm x 175mm (H x W x D), compact size enables panel space savings. Multi standards certified(CE,CB,CCC,cULus,EAC,KC,RCM,Marine) and Green Premium compliant (RoHs/Reach). Unique QR code provides quick access to complete product data.
The Schneider Electric high power contactor is rated for 1000 VAC or 460 VDC. This contactor has built-in bidirectional peak limiting coil technology. It is certified by CB Scheme, CCC, CULus, EAC, CE, UKCA, and EU-RO-MR by DNV-GL.
Rated breaking capacity: 1200 A at 440 V
Advanced version contactor
IP2x degree of protection on front face
8 kV rated impulse withstand voltage
Advanced version contactor
IP2x degree of protection on front face
8 kV rated impulse withstand voltage