Siemens, 3RB3 Overload Relay 1 NO/1 NC, 12A, 3 A F.L.C, 12A Contact Rating, 5.5 kW 3

Subtotal (1 unit)*

£99.29

(exc. VAT)

£119.15

(inc. VAT)

Add to Basket
Select or type quantity
In Stock
  • Plus 4 unit(s) shipping from 27 April 2026
  • Plus 2 unit(s) shipping from 27 April 2026
Need more? Click ‘Check delivery dates’ to find extra stock and lead times.
Units
Per unit
1 +£99.29

*price indicative

RS Stock No.:
706-0807
Distrelec Article No.:
301-24-275
Mfr. Part No.:
3RB3026-1SB0
Brand:
Siemens
Find similar products by selecting one or more attributes.
Select all

Brand

Siemens

Product Type

Overload Relay

FLC Motor Rating

12, 3A

Relay Contact Current

12A

Mount Type

Direct

Series

3RB3

Power Rating

5.5kW

Pole and Throw Configuration

3

Terminal Type

Screw

Normal State Configuration

1 NO/1 NC

IP Rating

IP20

Reset Method

Automatic & Manual

Number of Auxiliary Contacts

2

Width

45mm

Adjustable Current Range

3 to 12 A

Minimum Operating Temperature

-25°C

Maximum Operating Temperature

60°C

Length

69.7mm

Contact Voltage

690V ac

Standards/Approvals

CSA Approved, IEC 61000-4-4, IEC 61508, CCC approved, IEC 81346-2, EAC Approved, CE Approved, IEC 65029, IEC 61000-4-5, IEC 61000-4-6, IEC 60068-2-27, IEC 61000-4-2, UL Approved, IEC 61000-4-3

Depth

83.5mm

Supply Voltage

690V ac

COO (Country of Origin):
CZ

Solid State Overload Relay - 3RB range


3RB30 and 3RB31 solid-state overload relays up to 80 A with internal power supply have been designed for current-sensitive protection of loads with normal and heavy starting against excessive temperature rises due to overload, phase unbalance or phase failure

Switch position indicator and test function

Trip class setting/internal ground-fault detection

Selector switch for manual/automatic reset

Class 10 and Class 20

Direct mounting

PTB 09 ATEX 3001 Ex II (2) GD

Electronic Overload Relays


The 3RB2 range of Solid State Electronic overloads can be connected directly to Siemens SIRIUS contactors to provide accurate motor overload protection with enhanced single phase sensitivity,Application: Protection of 3 phase AC motors in sinusoidal 50/60Hz network. These relays are not suitable for the protection of single phase or DC loads,Select according to motor full load current and contactor frame size e,g. S00

Approvals

CE, UL, CSA