Schneider Electric LT3S Thermistor Protection Unit 1NO + 1NC, 100 VA, 24 → 230 Vac/dc, TeSys
- RS Stock No.:
- 261-5711
- Mfr. Part No.:
- LT3SA00MW
- Brand:
- Schneider Electric
Bulk discount available
Subtotal (1 unit)*
£179.79
(exc. VAT)
£215.75
(inc. VAT)
Stock information currently inaccessible - Please check back later
Units | Per unit |
|---|---|
| 1 - 9 | £179.79 |
| 10 - 14 | £169.01 |
| 15 + | £161.83 |
*price indicative
- RS Stock No.:
- 261-5711
- Mfr. Part No.:
- LT3SA00MW
- Brand:
- Schneider Electric
Specifications
Technical Reference
Legislation and Compliance
Product Details
Find similar products by selecting one or more attributes.
Select all | Attribute | Value |
|---|---|---|
| Brand | Schneider Electric | |
| Select all | ||
|---|---|---|
Brand Schneider Electric | ||
RoHS Status: Not Applicable
Schneider Electric T3SA00MW LT3SA TeSys LT3 PTC Probe Relay.
Features and Benefits.
- Automatic reset.
- Thermistor protection unit.
- Contacts 2 C/O multi voltage.
- Rated operational voltage 250 V AC 50/60 Hz for output control relay.
- Signal function - Fault indication, Voltage indication.
- Probe interchangeability - Label mark A conforming to IEC 60034-11.
- Power consumption (hold in) – 1 W, 2.5 VA.
- Number of probes 0 .. 6.
- Input voltage - < 2.5 V (1500 Ohm) for probe, < 7.5 V (4000 Ohm) for probe conforming to IEC 60034-11.
- Terminal connections – Power circuit – Cage type.
- Height 100 mm.
- Width 22.5 mm.
- Depth 100 mm.
- Net weight 0.22 kg.
Standards
IEC 60947-8 IEC 60034-11 VDE 0660.
IP20 conforming to IEC 60529 IP20 conforming to VDE 0106.
Vibrations resistance - 1 gn 25...150 Hz conforming to IEC 60068-2-6, 2.5 gn 2...25 Hz conforming to IEC 60068-2-6.
Shock resistance - 5 gn 11 ms conforming to IEC 60068-2-27.
Resistance to electrostatic discharge level 3 conforming to IEC 61000-4-2.
Resistance to fast transient level 3 conforming to IEC 61000-4-4.
Surge resistance 1.2/50-8/20 level 4 conforming to IEC 61000-4-5.
Susceptibility to electromagnetic fields level 3 conforming to IEC 61000-4-3.
Immunity to microbreaks and voltage drops conforming to IEC 61000-4-11.
IP20 conforming to IEC 60529 IP20 conforming to VDE 0106.
Vibrations resistance - 1 gn 25...150 Hz conforming to IEC 60068-2-6, 2.5 gn 2...25 Hz conforming to IEC 60068-2-6.
Shock resistance - 5 gn 11 ms conforming to IEC 60068-2-27.
Resistance to electrostatic discharge level 3 conforming to IEC 61000-4-2.
Resistance to fast transient level 3 conforming to IEC 61000-4-4.
Surge resistance 1.2/50-8/20 level 4 conforming to IEC 61000-4-5.
Susceptibility to electromagnetic fields level 3 conforming to IEC 61000-4-3.
Immunity to microbreaks and voltage drops conforming to IEC 61000-4-11.