Specifications
Technical Reference
Legislation and Compliance
Product Details
Find similar products by selecting one or more attributes.
Select all | Attribute | Value |
---|---|---|
Brand | Jumo | |
Minimum Temperature | 0°C | |
Maximum Temperature | 100°C | |
Thermostat Type | Capillary | |
Switch Configuration | NC | |
Reset Type | Automatic | |
Mounting Type | Surface Mount | |
Select all | ||
---|---|---|
Brand Jumo | ||
Minimum Temperature 0°C | ||
Maximum Temperature 100°C | ||
Thermostat Type Capillary | ||
Switch Configuration NC | ||
Reset Type Automatic | ||
Mounting Type Surface Mount | ||
- COO (Country of Origin):
- DE
The Jumo Mechanical Surface Mounting Double Thermostat is very robust and can also be used in rough conditions. The electrical connection is made by screw terminals connected directly to the installed microswitches, which can directly switch a maximum permissible switching capacity of AC 230 V / 10 A. The measuring systems used operate according to the fluid expansion principle and can be used up to a maximum permissible probe temperature of 125°C without any problems and the protection tube made of nickel plated brass has a diameter of 15 mm. The maximum permissible ambient temperature at the case (protection class IP54) is 80 °C. The thermostat can be used very flexibly and is used in heating, air conditioning and ventilation technology as well as in the plastics industry, apparatus and mechanical engineering as well as in furnace construction, in district heating transfer stations and for temperature monitoring in laboratories and climatic chambers.
Approved according to DIN EN 14597 and an EAC approval
Device comprises two temperature monitors
Desired switch off temperature can be set independently of each other on a scale
With the help of a screwdriver after removing the case cover
Temperature monitors have a high switching point accuracy of +0/-1.5% in the upper third of the scale
Switching differential (hysteresis) of approx. 3 to 4% of the scale range
After reaching the switch off point and temperature monitors switch off
No additional auxiliary power is required for temperature measurement
Fastened by a thread G 1/2 Form A according to DIN 3852/2
Device comprises two temperature monitors
Desired switch off temperature can be set independently of each other on a scale
With the help of a screwdriver after removing the case cover
Temperature monitors have a high switching point accuracy of +0/-1.5% in the upper third of the scale
Switching differential (hysteresis) of approx. 3 to 4% of the scale range
After reaching the switch off point and temperature monitors switch off
No additional auxiliary power is required for temperature measurement
Fastened by a thread G 1/2 Form A according to DIN 3852/2