Jumo 701150 Controller 2 Input, 4 Output Analogue, 20 → 30 V ac/dc Supply Voltage Controller
- RS Stock No.:
- 278-879
- Mfr. Part No.:
- 701150/8-01-0253-2001-23/005,058
- Brand:
- Jumo
Subtotal (1 unit)*
£560.60
(exc. VAT)
£672.72
(inc. VAT)
FREE delivery for orders over £50.00
Temporarily out of stock
- Shipping from 03 November 2025
Need more? Click ‘Check delivery dates’ to find extra stock and lead times.
Units | Per unit |
---|---|
1 + | £560.60 |
*price indicative
- RS Stock No.:
- 278-879
- Mfr. Part No.:
- 701150/8-01-0253-2001-23/005,058
- Brand:
- Jumo
Specifications
Technical Reference
Legislation and Compliance
Product Details
Find similar products by selecting one or more attributes.
Select all | Attribute | Value |
---|---|---|
Brand | Jumo | |
Output Type | Analogue | |
Supply Voltage | 20 → 30 V ac/dc | |
Number of Inputs | 2 | |
Number of Outputs | 4 | |
Control Type | Controller | |
Series | 701150 | |
Select all | ||
---|---|---|
Brand Jumo | ||
Output Type Analogue | ||
Supply Voltage 20 → 30 V ac/dc | ||
Number of Inputs 2 | ||
Number of Outputs 4 | ||
Control Type Controller | ||
Series 701150 | ||
- COO (Country of Origin):
- DE
The Jumo Configurable safety temperature limiter/ monitor according to DIN EN 14597 with 1oo2D architecture with SIL and PL approval is equipped with two universal analogue inputs and two relay outputs (pre- and limit value alarm) as well as a universal analogue output. The switching capacity of the relay contacts is AC 250 V, 3 A, 50 Hz (resistive load). The pre-alarm is adjustable as absolute or as distance from the limit value. This occurs after the sensor temperature has fallen below the set limit value by the amount of the switching difference (setting: max-alarm). The automatic resetting is carried out with setting Min-Alarm after the sensor temperature has risen above the set limit value by the amount of the switching difference. When used as a safety temperature limiter STB (protection temperature limiter for heat generating plants), the reset is performed manually or with a tool. The power supply range is from AC 110 to 240 V +10 % /-15 %, 48 to 63 Hz.
Front side features an LC display with backlighting and plain text
Safety temperature limiter and monitor detect and prevent hazards early
Monitor thermotechnical processes and restore safe operation in case of faults
Analog input supports various sensors or standard signals
Limit exceedance is indicated by LEDs and relay output switches to a safe state
Meets DIN EN 61508 DIN EN 13849 and Machinery Directive 2006/42/EC
STW operates with automatic reset for heat-generating systems
Safety temperature limiter and monitor detect and prevent hazards early
Monitor thermotechnical processes and restore safe operation in case of faults
Analog input supports various sensors or standard signals
Limit exceedance is indicated by LEDs and relay output switches to a safe state
Meets DIN EN 61508 DIN EN 13849 and Machinery Directive 2006/42/EC
STW operates with automatic reset for heat-generating systems