PR Electronics 9100 Series Universal Converter, Universal Input, Current, Relay Output, 19.2 → 31.2V dc Supply
- RS Stock No.:
- 796-7042
- Mfr. Part No.:
- 9116B1
- Brand:
- PR Electronics
Subtotal (1 unit)*
£424.40
(exc. VAT)
£509.28
(inc. VAT)
FREE delivery for orders over £50.00
In Stock
- 28 unit(s) ready to ship
- Plus 12 unit(s) ready to ship from another location
- Plus 11 unit(s) shipping from 05 November 2025
Need more? Click ‘Check delivery dates’ to find extra stock and lead times.
Units | Per unit |
---|---|
1 + | £424.40 |
*price indicative
- RS Stock No.:
- 796-7042
- Mfr. Part No.:
- 9116B1
- Brand:
- PR Electronics
Specifications
Technical Reference
Legislation and Compliance
Product Details
Find similar products by selecting one or more attributes.
Select all | Attribute | Value |
---|---|---|
Brand | PR Electronics | |
Module Type | Universal Signal Converter | |
Input Signal Type | Universal | |
Output Signal Type | Current, Relay | |
Supply Voltage | 19.2 → 31.2V dc | |
Operating Temperature Range | -20 → +60°C | |
Series | 9100 | |
Minimum Operating Temperature | -20°C | |
Maximum Operating Temperature | +60°C | |
Select all | ||
---|---|---|
Brand PR Electronics | ||
Module Type Universal Signal Converter | ||
Input Signal Type Universal | ||
Output Signal Type Current, Relay | ||
Supply Voltage 19.2 → 31.2V dc | ||
Operating Temperature Range -20 → +60°C | ||
Series 9100 | ||
Minimum Operating Temperature -20°C | ||
Maximum Operating Temperature +60°C | ||
- COO (Country of Origin):
- DK
PR Electronics 9116B Ex Universal Converter
PR Electronics 9116B universal converter for the conversion and scaling of temperature, voltage, potentiometer and linear resistance signals. Featuring an advanced relay configuration, the 9116B signal conditioner provides relay functionality such as setpoint, window, delay, sensor error indication and power monitoring. The 9116B has been designed, developed and certified for use in SIL 2 applications according to the requirements of IEC 61508.
Features and Benefits
• Can be mounted in the safe area or in zone 2 / cl. 1 div. 2 and receive signals from zone 0, 1, 2 and zone 20, 21, 22 including M1 / Class I/II/III, Div. 1, Gr. A-G
• Configuration and monitoring by way of detachable display front (PR 4501/4511)
• 2.6 kVac galvanic isolation between input, output and supply
• Active / passive mA output via the same two terminals
• Monitoring of error events and cable breakage via the individual status relay
• Designed, developed and certified for use in SIL 2 applications
• Front LED indicates operation status and malfunction
• DIN rail mounting
• Active and passive mA input
• Active or passive output via the same two terminals
• Configuration and monitoring by way of detachable display front (PR 4501/4511)
• 2.6 kVac galvanic isolation between input, output and supply
• Active / passive mA output via the same two terminals
• Monitoring of error events and cable breakage via the individual status relay
• Designed, developed and certified for use in SIL 2 applications
• Front LED indicates operation status and malfunction
• DIN rail mounting
• Active and passive mA input
• Active or passive output via the same two terminals
Programming
The 9116B universal transmitters are programmable via the PR 4510 detachable display module (238-0641). The 4510 module allows the programming of the vast array of input and output parameters easily and safely. Together with advanced functions including 2-point calibration, process simulation and diagnostics.
With a simple menu and explanatory text, the 4510 is extremely straightforward to navigate. Functions are clearly depicted on the 4-line LCD display even in low light conditions. Line 1 shows the input signal, line 2 shows the units, and line 3 shows analogue output or tag number. Line 4 shows the communication and relay status. In addition, the 4510 features password protection. Programming access can be blocked by assigning a password which is conveniently saved in the 9116B transmitter. This ensures a high degree of protection is maintained and prevents any unauthorised modifications to the configuration.
With a simple menu and explanatory text, the 4510 is extremely straightforward to navigate. Functions are clearly depicted on the 4-line LCD display even in low light conditions. Line 1 shows the input signal, line 2 shows the units, and line 3 shows analogue output or tag number. Line 4 shows the communication and relay status. In addition, the 4510 features password protection. Programming access can be blocked by assigning a password which is conveniently saved in the 9116B transmitter. This ensures a high degree of protection is maintained and prevents any unauthorised modifications to the configuration.
PR Electronics - Ex Interfaces