Broyce Controls L-Series signal conditioners use a QR barcode marking method allowing direct access to all technical data sheets, ensuring correct information is always at your finger tips!
Compact 17.5 mm DIN Rail housing
Microprocessor based
True R.M.S. monitoring measuring phase to phase (three wire) or phase to neutral (4-wire) voltages
Selectable nominal voltages to suit most popular three wire or 4-wire supply voltages
Monitors own supply and detects if one or more phases exceed the set Under or Over voltage trip levels
Detects incorrect phase sequence, phase loss and neutral loss1
Adjustments for Under and Over voltage trip levels
Adjustment for time delay
Independent relay outputs - Under voltage monitoring / Over voltage monitoring
2 x SPDT relay output 5A
Green LED indication for supply status
Individual Red LED indication for both relay statuses
UL Certification
Relay controllers manufactured using flame retardant material to UL94 VO
Electrical life: ≥150 000 operations
Suitable for use within ambient temperature environments from -20 to +60°C (except stock no. 361-1710 and 361-1681 which are suitable from -20 to +50°C)
Output relay contact rating specified at 250Vac
Attribute | Value |
---|---|
Monitoring Application | Voltage |
Supply Voltage | 400 V |
Contact Configuration | SPDT |
Electrical Phase | 3 |
Voltage Sensing Range | 243 → 540 V |
Phase Sensitivity | Phase Failure, Phase Sequence |
Time Delay | 0.2 → 10 s |
Special Features | Adjustment For Time Delay, Adjustments For Under And Over Voltage Trip Levels, Detects Incorrect Phase Sequence, Microprocessor Based, Phase Loss And Neutral Loss |
Minimum Operating Temperature | -20°C |
Terminal Type | Wire Lead |
Length | 89mm |
Mounting Type | DIN Rail |
Standards Met | CE, EN 61000-6-2, EN 61000-6-4, IEC, RoHS Complaint |
Minimum Voltage Sensed | 243 V |
Operating Temperature Range | -20 → +60 °C |
Maximum Operating Temperature | +60°C |
Width | 17.5mm |
Height | 66.5mm |
Maximum Voltage Sensed | 540V |
Dimensions | 89 x 17.5 x 66.5 mm |