Merlin Gerin C60HB MCB Mini Circuit Breaker2P, 32A Curve B, 415V AC, 10 kA Breaking Capacity
- RS Stock No.:
- 200-1730
- Mfr. Part No.:
- C60HB232
- Brand:
- Merlin Gerin
Image representative of range
Unavailable
RS will no longer stock this product.
- RS Stock No.:
- 200-1730
- Mfr. Part No.:
- C60HB232
- Brand:
- Merlin Gerin
Specifications
Technical Reference
Legislation and Compliance
Product Details
Find similar products by selecting one or more attributes.
Select all | Attribute | Value |
|---|---|---|
| Brand | Merlin Gerin | |
| Number of Poles | 2 | |
| Current Rating | 32A | |
| Tripping Characteristics | Type B | |
| Rated AC Voltage | 415V | |
| Breaking Capacity at Maximum Voltage Rating | 10 kA | |
| Series | C60HB | |
| Width | 36mm | |
| Length | 81mm | |
| Depth | 76mm | |
| Select all | ||
|---|---|---|
Brand Merlin Gerin | ||
Number of Poles 2 | ||
Current Rating 32A | ||
Tripping Characteristics Type B | ||
Rated AC Voltage 415V | ||
Breaking Capacity at Maximum Voltage Rating 10 kA | ||
Series C60HB | ||
Width 36mm | ||
Length 81mm | ||
Depth 76mm | ||
C60HB, Type B
Type B characteristic offers instantaneous short circuit response of 3-5 x normal rated current and overload response of 1.05 - 1.3 x normal rated current. This makes it suitable for most general circuit protection applications.
Positive indicator of contact position via front switch lever
Terminal shields for single and double pole versions
Auxiliary Changeover Switch which can be used as an indicating or control device to monitor the ON or OFF position of the MCB
Operating temperature of -30°C to +60°C
Compliance with BS EN 60898
Module widths: 1 pole 18mm, 2 pole 36mm and 3 pole 54mm
Terminal Capacity: 1→20A 25mm2, 32→63A 35mm2
Terminal shields for single and double pole versions
Auxiliary Changeover Switch which can be used as an indicating or control device to monitor the ON or OFF position of the MCB
Operating temperature of -30°C to +60°C
Compliance with BS EN 60898
Module widths: 1 pole 18mm, 2 pole 36mm and 3 pole 54mm
Terminal Capacity: 1→20A 25mm2, 32→63A 35mm2
Standards
BS EN 60898