Broyce Control Level Controller - DIN Rail Mount, 230 V ac 2

Technical Reference
Legislation and Compliance
RoHS Certificate of Compliance
COO (Country of Origin): GB
Product Details

Floatless Level Controller with Alarm Output

Monitors level of a liquid in a tank or container
3 levels of monitoring; Low, High and Alarm
DIN rail mounting
Operate resistance; 4kΩ, release resistance; 15kΩ
Time delay: operate; ≤80ms, release; ≤160ms
1 km maximum distance between controller and probes
Ambient temperature; -20 to +60°C
Built in surge arresters protect each probe from lightning strikes
LED indication of probe/tank level status and for supply and relay output status
Dimensions (mm): H 85, W 70, D 63.6

Liquid Level Relays are used to monitor the levels of conductive liquids, and are available in Up/Down, Minimum, Maximum, and Fill/Empty variations. Liquid Level Relays are straightforward to install and safe to use.

Application Examples

Liquid Level Relays (Conductive Level Sensors) are used in a wide variety of applications including waste water management and the monitoring and management of corrosive liquid media, and designed specifically to provide for the:

Monitoring and control of liquid levels
Protection of pumps against dry running
Ability to detect liquid leaks in a system
Control of media mixing ratios
Control of liquid levels

Specifications
Attribute Value
Number of Inputs 2
Mounting Style DIN Rail Mount
Probe Voltage 8V ac
Supply Voltage 230 V ac
Overall Length 85mm
Overall Width 70mm
Overall Depth 63.5mm
Minimum Operating Temperature -20°C
Maximum Operating Temperature +60°C
23 In stock for FREE next working day delivery
Price Each
£ 85.01
(exc. VAT)
£ 102.01
(inc. VAT)
Units
Per unit
1 - 4
£85.01
5 +
£82.40
Related Products
The K7L-AT50 liquid leakage sensor amplifier by Omron ...
Description:
The K7L-AT50 liquid leakage sensor amplifier by Omron can detect a wide variety of liquids ranging from water to chemicals with low conductivity. It internally oscillates AC signals provided to the Sensing Band, protecting it from electric corrosion and ensuring safe operation.There are four sensing ranges available, ensuring detection is ...
The Flowline USB Fob adapter enables you to ...
Description:
The Flowline USB Fob adapter enables you to set up your level sensor using the free Webcal download and your computer. • Download Webcal to your computer • Connect the EchoSonic to USB Fob using the colour coded terminals • Plug the USB into your Computer • Open Webcal and ...
Maximum/Minimum Liquid Level Relays are suitable for a ...
Description:
Maximum/Minimum Liquid Level Relays are suitable for a number of applications including fill and drain monitoring of tanks. Single-pole electrodes sense a change in resistance, energising the circuit if the liquid exceeds the maximum level, and de-energising if the liquid level drops below the minimum level. Monitoring and control of ...
Often used to monitor liquid levels in pump ...
Description:
Often used to monitor liquid levels in pump control systems and dry running protection for submersible pumps, Fill/Empty Level Liquid Relays measuring principle is based on a change in resistance sensed by single-pole electrodes. Measuring, output and supply circuits are electrically isolated to prevent interference. Monitoring and control of liquid ...