PULS DIMENSION Q Switched Mode DIN Rail Power Supply, 100 → 240V ac ac Input, 48V dc dc Output, 10A Output, 480W

Subtotal (1 unit)*

£336.27

(exc. VAT)

£403.52

(inc. VAT)

Add to Basket
Select or type quantity
In Stock
  • 10 unit(s) ready to ship
  • Plus 39 unit(s) ready to ship from another location
  • Plus 8 unit(s) shipping from 13 October 2025
Need more? Click ‘Check delivery dates’ to find extra stock and lead times.
Units
Per unit
1 +£336.27

*price indicative

Alternative

This product is not currently available. Here is our alternative recommendation.

RS Stock No.:
670-0674
Distrelec Article No.:
169-96-535
Mfr. Part No.:
QS20.481
Brand:
PULS
Find similar products by selecting one or more attributes.
Select all

Brand

PULS

Series

DIMENSION Q

Type

Switched Mode

Electrical Phase

1

Number of Outputs

1

AC or DC Input Voltage

ac

Input Voltage

100 → 240V ac

AC or DC Output Voltage

dc

Output Voltage

48V dc

Output Current

10A

Dimensions

82 x 124 x 127mm

Height

124mm

Width

82mm

Depth

127mm

Mounting Type

DIN Rail Mount

Minimum Temperature

-25°C

Load Regulation

100mV

MTBF

840000h

Maximum Temperature

+70°C

Ripple And Noise

100mV Pk-Pk

COO (Country of Origin):
CZ

PULS DIN Rail Power Supply


The PULS DIMENSION Q series single-phase DIN-rail switch-mode power supply has an adjustable output voltage ranging between 48VDC and 55VDC with 10A current. This cost-optimised power supply is specifically designed with uncompromised quality and reliability for high-performance. This unit is equipped with an input voltage ranging between 100VAC and 240VAC. This power supplies diagnostic is easy due to the dry DC-ok contact, a green DC-ok LED and red overload LED. High immunity to transients and power surges as well as low electromagnetic emission make it usable in nearly every environment.

Features and Benefits


Light and compact
Easy to install
Quick-connect spring-clamp terminals
Efficiency is up to 94.3%
Power rating is 480W
Ripple factor and noise is 100mVpp
Very low no-load losses
Active power factor correction (PFC)
Negligible low inrush current surge
150% peak load capability
Safe hiccupPLUS overload mode
DC-OK signal with relay
Operation temperature ranges between -25°C and 70°C

Applications


Industrial control
Automation
Communication and instrumentation equipment

Certifications


IEC
UL approved
EN
SELV