Jumo Data Acquisition Receiver for Use with Data Acquisition
- RS Stock No.:
- 279-519
- Mfr. Part No.:
- 902931/10-8-10-23/000
- Brand:
- Jumo
Unavailable
RS will no longer stock this product.
Alternative
This product is not currently available. Here is our alternative recommendation.
Each
£444.58
(exc. VAT)
£533.50
(inc. VAT)
- RS Stock No.:
- 279-519
- Mfr. Part No.:
- 902931/10-8-10-23/000
- Brand:
- Jumo
Specifications
Technical Reference
Legislation and Compliance
Product Details
Find similar products by selecting one or more attributes.
Select all | Attribute | Value |
---|---|---|
Brand | Jumo | |
Accessory Type | Receiver | |
For Use With | Data Acquisition | |
Select all | ||
---|---|---|
Brand Jumo | ||
Accessory Type Receiver | ||
For Use With Data Acquisition | ||
- COO (Country of Origin):
- DE
The Jumo The Jumo Radio receiver is used in connection with suitable transmitters for mobile or stationary measurement of physical quantities. The use of trend-setting radio technology of the industrial radio frequency 868.4 MHz results in a significant reduction of the installation effort. Cable connections can be omitted, the radio-based sensor technology also works in rough industrial environments. If the optionally available antenna wall bracket with 3 m long antenna cable is used, the free field range is 300 m. The measured values received from the transmitter are converted and displayed in the receiver and are available as linear current or voltage signals (0(4) to 20 mA, 0 to 10 V) and via digital interface RS485. All four analog outputs of the receiver are galvanically isolated. The digital interface with Modbus protocol, a connection to higher-level systems, such as plant visualization software or Modbus master-capable paperless recorders, is possible.
The receiver in a DIN rail housing is designed for mounting on 35 x 7.5 mm top-hat rails according to DIN EN 60715
The screw terminals for the electrical connection are arranged in different levels
The cable cross-section may not exceed 2.5 mm2
A connection to AC 110 to 240 V +10/-15 %, 48 to 63 Hz serves as power supply
Operation and configuration is possible via the keyboard in conjunction with a two-line LCD display, or more conveniently through a setup program
Parameters such as filter constants, offset, alarms and slave pointer (minimum and maximum value memory) can be set separately for each channel
For this purpose, there is a plug on the front for a PC interface with TTL/RS232 or USB/TTL converter for connection between receiver and PC
The supplied Lambda/4 antenna with an impedance of 50 Ohm can be screwed on directly or mounted externally
The screw terminals for the electrical connection are arranged in different levels
The cable cross-section may not exceed 2.5 mm2
A connection to AC 110 to 240 V +10/-15 %, 48 to 63 Hz serves as power supply
Operation and configuration is possible via the keyboard in conjunction with a two-line LCD display, or more conveniently through a setup program
Parameters such as filter constants, offset, alarms and slave pointer (minimum and maximum value memory) can be set separately for each channel
For this purpose, there is a plug on the front for a PC interface with TTL/RS232 or USB/TTL converter for connection between receiver and PC
The supplied Lambda/4 antenna with an impedance of 50 Ohm can be screwed on directly or mounted externally
Related links
- Jumo Data Acquisition Receiver for Use with Data Acquisition
- Jumo Data Acquisition Receiver for Use with T01 Series
- Jumo Data Acquisition Module for Use with Data Acquisition
- Jumo 902928 Temperature Transmitter Pt1000 Input, 18 → 30 V dc
- Jumo diraVIEW Digital Indicator
- Jumo di 308 LCD Process Indicator, 48mm x 96mm
- Jumo 202565 Temperature Transmitter Pt100 Input, 110 → 240 v ac
- Jumo Temperature Transmitter PT100 Input, 110 → 240 V ac