Siemens 3RB3 Solid State Overload Relay NO/NC, 50 A Contact Rating, 3 → 11 kW, 250 V ac, 4P, Sirius Innovation
- RS Stock No.:
- 866-5488
- Mfr. Part No.:
- 3RB31234QB0
- Brand:
- Siemens
Currently unavailable
We don’t know if this item will be back in stock, it is being discontinued by the manufacturer.
- RS Stock No.:
- 866-5488
- Mfr. Part No.:
- 3RB31234QB0
- Brand:
- Siemens
Specifications
Technical Reference
Legislation and Compliance
Product Details
Find similar products by selecting one or more attributes.
Select all | Attribute | Value |
---|---|---|
Brand | Siemens | |
Contact Current Rating | 50 A | |
Range | Sirius Innovation | |
Pole Configuration | 4P | |
Series | 3RB3 | |
Mounting Style | Direct Mount | |
Power Rating | 3 → 11 kW | |
Normal State Configuration | NO/NC | |
Reset Method | Automatic, Manual, Remote | |
Terminal Type | Screw | |
Width | 89mm | |
Number Of Auxiliary Contacts | 2 | |
Depth | 80mm | |
Length | 45mm | |
Maximum Operating Temperature | +60°C | |
Minimum Operating Temperature | -25°C | |
Operating Temperature Range | -25 → +60 °C | |
Control Voltage | 250 V ac | |
Contact Voltage Rating | 690 V ac | |
Select all | ||
---|---|---|
Brand Siemens | ||
Contact Current Rating 50 A | ||
Range Sirius Innovation | ||
Pole Configuration 4P | ||
Series 3RB3 | ||
Mounting Style Direct Mount | ||
Power Rating 3 → 11 kW | ||
Normal State Configuration NO/NC | ||
Reset Method Automatic, Manual, Remote | ||
Terminal Type Screw | ||
Width 89mm | ||
Number Of Auxiliary Contacts 2 | ||
Depth 80mm | ||
Length 45mm | ||
Maximum Operating Temperature +60°C | ||
Minimum Operating Temperature -25°C | ||
Operating Temperature Range -25 → +60 °C | ||
Control Voltage 250 V ac | ||
Contact Voltage Rating 690 V ac | ||
RoHS Status: Not Applicable
- COO (Country of Origin):
- DE
Solid State Overload Relay - 3RB range
3RB30 and 3RB31 solid-state overload relays up to 80 A with internal power supply have been designed for current-sensitive protection of loads with normal and heavy starting against excessive temperature rises due to overload, phase unbalance or phase failure
Switch position indicator and test function
Trip class setting/internal ground-fault detection
Selector switch for manual/automatic reset
Class 10 and Class 20
Direct mounting
PTB 09 ATEX 3001 Ex II (2) GD
Trip class setting/internal ground-fault detection
Selector switch for manual/automatic reset
Class 10 and Class 20
Direct mounting
PTB 09 ATEX 3001 Ex II (2) GD
Approvals
CE, UL, CSA
Electronic Overload Relays
The 3RB2 range of Solid State Electronic overloads can be connected directly to Siemens SIRIUS contactors to provide accurate motor overload protection with enhanced single phase sensitivity,Application: Protection of 3 phase AC motors in sinusoidal 50/60Hz network. These relays are not suitable for the protection of single phase or DC loads,Select according to motor full load current and contactor frame size e,g. S00