Bicotest T631 TDR Cable Fault Locator, 1200m, RS232C Interface

  • RS Stock No. 267-1878
  • Mfr. Part No. 10/T631/3/A
  • Brand Bicotest
Technical Reference
Legislation and Compliance
RoHS Status: Not Applicable
Product Details
Ranges 13 ranges 0 to 3m up to 0m to 12km at pvf 0.67 zoom x2, x4, x8 dependant on range
Accuracy ±0.2% of range at 12km
Resolution ±0.05% of range at 12km
Gain 60dB max. selectable in 6dB steps
Sensitivity 15mv for full scale deflection
Return loss measurement 0 to 30dBR1
Propagation velocity pvf: 0.300 to 0.999 variable auto and manual
v: 90 to 300m/μs
v/2: 45 to 150m/μs
Pulse characteristics  
Amplitude 2.5V
Widths 2, 10, 30, 100, 300 and 1200ηS auto or manual selection
Output impedance 50, 75 or 93Ω user selectable
Noise reduction 16MHz low pass
Display High resolution LCD display with switchable back light
Modes Direct, direct and memory, direct minus memory only
Interface RS-232C to PC or printer
Power Internal Ni-Cd ’C’ type batteries giving 12
hours operation, auto power off at 5mins
External d.c. 12V-20V operating, min 15V for charging
Operating temp -5 → +50 °C
93% RH at 40 °C
Dimensions 300 x 183 x 75 mm
Weight 2.5 kg

Supplied with

X600 traceability software, rechargeable batteries, charger, operating manual, test lead, field carry case and accessories pouch.

Specifications
Attribute Value
Best Accuracy ±0.5 %
Maximum Range 1200m
Resolution 0.05 %
Cable Type CCTV, Coaxial CATV, Data Communication, HV Mains
Maximum Pulse Width 1200ns
Minimum Pulse Width 2ns
Pulse Amplitude 2.5V
Output Impedance 93Ω
Velocity Factor/Propagation Velocity 300m/µs
Interface Type RS232C
Battery Life 12 h
Battery Type C
Display Type LCD
Power Source Battery
Weight 2.5kg
Width 183mm
Height 75mm
Dimensions 300 x 183 x 75mm
Minimum Operating Temperature -5°C
Maximum Operating Temperature +50°C
Length 300mm
Model Number p T631
Discontinued product