Ranges | 13 ranges 0 to 3m up to 0m to 12km at pvf 0.67 zoom x2, x4, x8 dependant on range |
Accuracy | ±0.2% of range at 12km |
Resolution | ±0.05% of range at 12km |
Gain | 60dB max. selectable in 6dB steps |
Sensitivity | 15mv for full scale deflection |
Return loss measurement | 0 to 30dBR1 |
Propagation velocity | pvf: 0.300 to 0.999 variable auto and manual v: 90 to 300m/μs v/2: 45 to 150m/μs |
Pulse characteristics | |
Amplitude | 2.5V |
Widths | 2, 10, 30, 100, 300 and 1200ηS auto or manual selection |
Output impedance | 50, 75 or 93Ω user selectable |
Noise reduction | 16MHz low pass |
Display | High resolution LCD display with switchable back light |
Modes | Direct, direct and memory, direct minus memory only |
Interface | RS-232C to PC or printer |
Power | Internal Ni-Cd C type batteries giving 12 hours operation, auto power off at 5mins External d.c. 12V-20V operating, min 15V for charging |
Operating temp | -5 → +50 °C 93% RH at 40 °C |
Dimensions | 300 x 183 x 75 mm |
Weight | 2.5 kg |
X600 traceability software, rechargeable batteries, charger, operating manual, test lead, field carry case and accessories pouch.
Attribute | Value |
---|---|
Best Accuracy | ±0.5 % |
Maximum Range | 1200m |
Resolution | 0.05 % |
Cable Type | CCTV, Coaxial CATV, Data Communication, HV Mains |
Maximum Pulse Width | 1200ns |
Minimum Pulse Width | 2ns |
Pulse Amplitude | 2.5V |
Output Impedance | 93Ω |
Velocity Factor/Propagation Velocity | 300m/µs |
Interface Type | RS232C |
Battery Life | 12 h |
Battery Type | C |
Display Type | LCD |
Power Source | Battery |
Weight | 2.5kg |
Width | 183mm |
Height | 75mm |
Dimensions | 300 x 183 x 75mm |
Minimum Operating Temperature | -5°C |
Maximum Operating Temperature | +50°C |
Length | 300mm |
Model Number p | T631 |