Product Details

IL9151 - level relay with two separately operating changeovers

The IL9151 is used for

Level monitoring and control of conductive liquids and powders, e.g. maximum and minimum fill level, protection against overfilling and dry running
Monitoring and control of the mix ratio for conductive liquids
General resistance monitoring tasks, e.g. recording temperature limits with PTC
Contact protection relay with delay

Features

In accordance with IEC 255, VDE 0435 Section 303
3 electrode connections for 2-point or 1-point level control
The measuring circuit galvanically isolated from the mains is immune from high levels of interference
Max. lead length to the electrodes: 1500 m
Wide setting range of 4 → 450 kΩ, which enables differentiation between liquid and foam
Response and fallback delay: 0.2 → 20 s adjustable separately for MIN and MAX level
Programmable for: 2 separately controlled output relays for MIN and MAX level or jointly controlled output relays in 2-point hysteresis level control
Programmable for: Operating or rest current principle
Measuring circuit for electrodes works on AC voltage generated internally in the device (approx. 30 Hz); therefore no electrolysis occurrence in the fluid
LEDs to indicate operational readiness and contact position
2 output relays each with 1 changeover
35 mm overall width

Liquid Level Relays are used to monitor the levels of conductive liquids, and are available in Up/Down, Minimum, Maximum, and Fill/Empty variations. Liquid Level Relays are straightforward to install and safe to use.

Application Examples

Liquid Level Relays (Conductive Level Sensors) are used in a wide variety of applications including waste water management and the monitoring and management of corrosive liquid media, and designed specifically to provide for the:

Monitoring and control of liquid levels
Protection of pumps against dry running
Ability to detect liquid leaks in a system
Control of media mixing ratios
Control of liquid levels

1 In stock for delivery within 1 working days
Price Each
£ 121.81
(exc. VAT)
£ 146.17
(inc. VAT)
Units
Per unit
1 - 2
£121.81
3 +
£116.85
Not available for guaranteed pre 9am/10am delivery
Related Products
For AC and DC systems Type BTo detect ...
Description:
For AC and DC systems Type BTo detect earth faults in grounded voltage systems4 setting ranges from 10 mA to 3 AManual reset, with alarm and pre-warningWith adjustable switching delayEnergized or de-energized on tripLED indicator for operation, pre-alarm and alarmWith test functionLED-chain indicates fault currentAs option with analogue outputBroken wire ...
For single and 3-phase AC-systems up to 0 ...
Description:
For single and 3-phase AC-systems up to 0 ... 500 V and 10 ... 1000 HzMonitors also disconnected voltage systemsAdjustable tripping value RALof 5 ... 100 kΩDe-energized on tripAuxiliary voltage, measuring circuit and output contacts are galvanically separatedManual and auto resetWith test and reset buttonConnections for external test and reset ...
Safe standstill detection on 3and single-phase motorsNo external ...
Description:
Safe standstill detection on 3and single-phase motorsNo external sensors necessaryIndependent of directionBroken wire detectionForcibly guided safety contacts:3 NO contacts, 1 NC contact for AC 250 V2 semiconductor monitoring outputs1 monitoring output (NO contact)Adjustable voltage settingAdjustable standstill time delayLED indicators for standstill, event of line breakage and operation voltageSuitable for operation ...
No external sensors necessaryIndependent of directionBroken wire detectionForcibly ...
Description:
No external sensors necessaryIndependent of directionBroken wire detectionForcibly guided safety contacts:3 NO contacts, 1 NC contact for AC 250 V2 semiconductor monitoring outputs1 monitoring output (NO contact)Adjustable voltage settingAdjustable standstill time delayLED indicators for standstill, event of line breakage and operation voltageSuitable for operation with invertersWidth 45 mmAdvantages / Customer ...