- RS Stock No.:
- 240-9049
- Mfr. Part No.:
- AI898 DC24V 6kOhm UH=AC45-400Hz 230V
- Brand:
- Dold
Available to back order for despatch 06/05/2024, delivery within 2 working days
Not available for guaranteed pre 9am/10am delivery
Added
Price Each
£362.40
(exc. VAT)
£434.88
(inc. VAT)
Units | Per unit |
1 + | £362.40 |
- RS Stock No.:
- 240-9049
- Mfr. Part No.:
- AI898 DC24V 6kOhm UH=AC45-400Hz 230V
- Brand:
- Dold
Technical Reference
Legislation and Compliance
- COO (Country of Origin):
- DE
Product Details
Insulation monitor for direct current networks, AI898
Fixed response time 6 kΩ
LED display for operational readiness and earth fault
1 changeover
Overall width 45 mm
LED display for operational readiness and earth fault
1 changeover
Overall width 45 mm
The AI898 insulation monitor displays the insulation resistance of unearthed direct current networks to earth. It does not detect symmetrical earth faults. In practice, these faults are generally insignificant.
The AI898 works on the quiescent current principle, for example when the auxiliary voltage is applied to terminals A1 → A2 the output relay is activated and the "ON" LED indicates that the insulation resistance RAN is not less than the minimum value. If insulation resistance falls below the response value, the output relay drops, the "ON" LED goes out and the second LED for "Earth fault" lights up.
A bridge between terminals LT1 and LT2 (inserted as standard) allows the AI898 to be programmed for memory storage behaviour; remove the bridge to programme hysteresis behaviour. The bridge can be replaced with a delete key with an NC contact. A test key (PT) tests the functional efficiency of the device (as per VDE 0435).
The AI898 works on the quiescent current principle, for example when the auxiliary voltage is applied to terminals A1 → A2 the output relay is activated and the "ON" LED indicates that the insulation resistance RAN is not less than the minimum value. If insulation resistance falls below the response value, the output relay drops, the "ON" LED goes out and the second LED for "Earth fault" lights up.
A bridge between terminals LT1 and LT2 (inserted as standard) allows the AI898 to be programmed for memory storage behaviour; remove the bridge to programme hysteresis behaviour. The bridge can be replaced with a delete key with an NC contact. A test key (PT) tests the functional efficiency of the device (as per VDE 0435).
Specifications
Attribute | Value |
---|---|
Monitoring Application | Insulation |
Voltage Sensing Range | 0.8 → 1.1 V |
Contact Configuration | SPDT |
Mounting Type | DIN Rail |
Time Delay | 0.4s |
Series | AI 898 |
Dimensions | 115 x 45 x 77mm |
Maximum Operating Temperature | +60°C |
Width | 45mm |
Minimum Operating Temperature | -20°C |
Operating Temperature Range | +60°C |
Length | 115mm |
Height | 77mm |
- RS Stock No.:
- 240-9049
- Mfr. Part No.:
- AI898 DC24V 6kOhm UH=AC45-400Hz 230V
- Brand:
- Dold
Related links
- Dold Thermistor Motor Protection Monitoring Relay DIN Rail
- Dold Speed Monitoring Relay DIN Rail
- Dold Insulation Monitoring Relay 3 Phase 0 → 500V ac, DIN Rail
- Dold Frequency Monitoring Relay DIN Rail
- Dold Current Monitoring Relay DIN Rail
- Dold Multifunction Monitoring Relay SPDT DIN Rail
- Dold Frequency Monitoring Relay 15 → 280V ac, DIN Rail
- Dold Standstill Monitoring Relay 3 Phase DIN Rail