Price Each | ||||
|---|---|---|---|---|
|
Please log in to see latest prices
Register / Log In
In stock for next working day delivery
| ||||
|
|
|
Specifications
| Breaking Capacity | 50 kA | |
| Current Range | 10 → 16 A | |
| Depth | 74mm | |
| Length | 90mm | |
| Number of Poles | 3P | |
| Voltage Rating | 415 V | |
| Width | 45mm |
Quickly find other suitable products by removing those features above which are not essential and clicking Find.
Find
Motor Protection Circuit Breakers
Designed to be used in conjunction with the Allen Bradley 100-C contactor range to provide type 2 co-ordination without oversizing of the contactor, in rating up to 22kW. The breaker may be customised to suit individual requirements.
Trip Class 10
Short circuit indicator provides a differentiation between short circuit and overload tripping
Phase Loss protection
Jump mechanism ensures fast closing or opening of contacts
'ON', 'OFF', 'TRIP' indication
Lockable in OFF position, emergency OFF switch
Adjustable thermal release with mechanical reset
Ambient temperature compensation (-20 to +60°C)
Front mounting trip/auxiliary contacts
Magnetic release 13 x thermal overload trip current max
Disconnector approval to IEC947-2
Main Switch/Emergency Off approval to IEC204-1
| Dimensions (mm) | |||
| Part No Prefix | Width | Height | Depth |
| 140M-C | 45 | 90 | 69.5 |
| 140M-D | 45 | 90 | 79.5 |
| 140M-F | 54 | 110 | 109.5 |